Buy 750-439 Wago 2-Channel NAMUR Digital Input Module Ex i

Purchase now: Wago 750-439 NAMUR Input Module

Purchase now: Atlantech Drives provides you the Wago 750-439, a specialized **2-Channel Digital Input Module** designed for **NAMUR sensors** in hazardous environments. This module is typically classified as **Intrinsically Safe (Ex i)**, meaning it includes integrated safety barriers (isolators) that limit the energy delivered to the sensor, preventing sparks that could ignite explosive atmospheres (Zone 0/1). It reads the status of proximity sensors, level switches, or mechanical contacts located in the hazardous area.

Technical Specifications and Diagnostics

The 750-439 supplies a defined voltage (approx. 8.2V) to the NAMUR sensor. It detects not only the «On/Off» state but also **Wire Break** and **Short Circuit** conditions. If the current drops near zero (wire cut) or spikes (short), the module sends a diagnostic error to the PLC and lights up a Red LED. This eliminates the need for external Zener barriers in the control cabinet, saving massive amounts of space and wiring time.

  • Part Number: 750-439 (Ref NAMUR Series).
  • Channels: 2 Digital Inputs.
  • Sensor Type: NAMUR (DIN EN 60947-5-6).
  • Protection Type: Ex i (Intrinsically Safe).
  • Diagnostics: Short Circuit / Wire Break.
  • Signal Current: On < 1.2 mA / Off > 2.1 mA.
  • Installation: Zone 2 (Module) -> Zone 0/1 (Sensor).
  • Bit Width: 2 bits data + 2 bits diag.

Expert Installation Advice: Blue Housings

Ex i modules are special. Expert Tip: Wago Ex i modules usually have a **blue housing** or a blue flag to distinguish them. You must install them in a dedicated block, powered by an Ex i Supply Module (like 750-625) which separates the «safe» 24V bus from the «intrinsically safe» power. Never place a standard white/grey module in the middle of the blue Ex i block, as it violates the safety clearance distances (creepage and clearance).

Frequently Asked Questions (FAQs)

Q: Can I connect a standard mechanical switch?
A: Yes, but to use the wire break supervision, you must install a specific resistor network (1kΩ / 10kΩ) at the switch contacts so the module sees the correct NAMUR current levels.

Q: Is this compatible with all couplers?
A: Yes, it works with standard PROFINET, Ethernet, or Modbus couplers, provided the power supply segment is configured correctly for Ex i.

Do you need more references from this brand? Explore our full catalog of Wago here.

Check Price & Availability!

Get a fast, no-obligation quote for this part.

Our technical team responds within 24-48 hours.

  • Express Worldwide Shipping
  • 100% Genuine OEM Parts

We can supply you this part. Just get in touch!

Logo Pagos Seguros