Key Technical Specifications
- Product Type: Standard control unit, TeSys U
- Overload Tripping Class: 10 (per IEC 60947-6-2 and UL 508)
- Rated Current (Ir): 0.35–1.4 A (adjustable)
- Short-Circuit Protection: 13 x Irmax
- Overcurrent Protection: 14.2 x Ir
- Motor Power Rating: 0.25 kW at 400 V (3-phase)
- Control Voltage: 24 V DC
- Compatible Power Bases: LUB12, LUB32, LUB38, LUB120, LUB320, LUB380
- Compatible Reversing Contactor Breakers: LU2B12BL, LU2B32BL, LU2B38BL
- Closing Current (Max.): 130 mA (LUB12); 220 mA (LUB32/LUB38)
- Sealed Current (Irms): 60 mA (LUB12); 80 mA (LUB32/LUB38)
- Opening Time (Control Circuit): 35 ms
- Closing Time (Control Circuit): 70 ms
- Ambient Temperature: -25°C to 70°C (-13°F to 158°F)
- Frequency Range: 40–60 Hz
- Enclosure Rating: IP40 (system level)
- Mounting: Plug-in module
- Approvals: IEC, UL, CSA, CCC, EAC, Marine (when used with a LUB power base); Green Premium (RoHS/REACh)
Design and Performance
Modular, Customizable Motor Starter Building Block
As part of the TeSys U modular motor control system, the LUCA1XBL plugs directly into a compatible LUB power base to form a complete starter, letting engineers assemble and wire the system before finalizing motor protection parameters and control voltage.
Comprehensive Motor Protection in One Module
Provides full protection for motors rated 0.35-1.4 A, combining Class 10 overload tripping, short-circuit protection at 13x Irmax, overcurrent protection at 14.2x Ir, phase loss detection, and insulation fault monitoring (equipment protection only) in a single plug-in unit.
Fast Configuration Changes Without Rewiring
Plug-in modules allow motor protection parameters or control voltages to be changed in seconds by simply swapping the control unit, without disturbing the existing power base wiring — ideal for retrofits or standardized panel designs.
Wide Operating Temperature Range
Rated for -25°C to 70°C operation, the LUCA1XBL supports reliable performance across demanding ambient conditions, from cold storage facilities to hot industrial environments.
Broad International Certification
When used with a compatible LUB power base, this control unit is certified to IEC, UL, CSA, CCC, EAC, and Marine standards, and is Green Premium compliant, supporting deployment across regulated global markets.