Key Technical Specifications

  • Product Type: Differential thermal overload relay, TeSys LRD
  • Relay Application: Motor protection
  • Overload Tripping Class: 10A (per IEC 60947-4-1)
  • Thermal Protection Adjustment Range: 23–32 A
  • Number of Poles: 3P
  • Rated Insulation Voltage (Ui): 1000 V (IEC 60947-4-1); 600 V (CSA/UL)
  • Rated Operational Voltage (Ue): 690 V AC, 0–400 Hz
  • Network Type: AC/DC
  • Tripping Threshold: 1.14 ±0.06 Ir (per IEC 60947-4-1)
  • Conventional Free Air Thermal Current (Ith): 5 A for signalling circuit
  • Permissible Current: 0.72 A at 500 V AC-15 for signalling circuit
  • Power Circuit Terminals: Screw clamp, 4–35 mm² (flexible or solid)
  • Control Circuit Terminals: Screw clamp, 1–2.5 mm² (flexible or solid)
  • Product Compatibility: LC1D80, LC1D95
  • Mounting Support: Plate with specific accessories
  • Ambient Temperature: -20°C to 60°C (without derating)

Design and Performance

Differential Protection for Higher-Power Motor Starters

As a differential thermal overload relay compensated with phase failure sensitivity, the LRD3353 protects larger three-phase motor circuits against overload and phase failure conditions when paired with LC1D80 or LC1D95 contactors.

High Insulation Voltage for Demanding Power Circuits

Rated for 1000 V insulation per IEC 60947-4-1, the LRD3353 supports higher-voltage industrial power distribution systems, extending overload protection to more demanding applications than lower-voltage relay variants.

Manual or Automatic Reset with Trip Indicator

A compensated relay design featuring a relay trip indicator, alongside selectable manual or automatic reset, gives operators clear fault status visibility and flexible control over restart behavior after an overload event.

Heavy-Gauge Terminal Capacity for High-Current Wiring

Power circuit screw clamp terminals accept conductors from 4 to 35 mm², accommodating the heavier cable gauges typical of the higher current range associated with LC1D80/LC1D95 motor starter assemblies.

Reliable, Proven TeSys Deca Platform

Part of the broader TeSys Deca thermal overload relay range — very reliable and covering motor ratings up to 150 A — the LRD3353 mounts directly onto same-size-ratio LC1D contactors with screw clamp connectors to form a compact, coordinated starter.

Why Buy the LRD3353 From Us

  • In stock and ready for immediate dispatch
  • Fast shipping on every order
  • Commercial advisory support to help you confirm the right LRD overload relay for your LC1D80/LC1D95 contactor
  • Competitive pricing — get a quote in minutes

Check Price & Availability!

Get a fast, no-obligation quote for this part.

Our technical team responds within 24-48 hours.

  • Express Worldwide Shipping
  • 100% Genuine OEM Parts

We can supply you this part. Just get in touch!

Logo Pagos Seguros
Trustpilot logoTrustpilot
Great rating
TrustScore 4.4
13 reviews