A9F74125 Schneider Electric – Acti9 iC60N MCB, 1 Pole, 25 A, C Curve, 6000 A (IEC 60898-1) / 10 kA (IEC 60947-2)
The A9F74125 is the 25 A, single-pole, C-curve version of Schneider Electric’s Acti9 iC60N miniature circuit breaker. It sits one step above the 20 A rating and is typically used for heavier final circuits: larger socket-outlet circuits, small heating loads, HVAC units, single-phase motors and sub-distribution feeds. The C tripping curve tolerates the moderate inrush currents of motors and transformers without nuisance tripping, while still clearing short circuits quickly.
A9F74125 at a Glance
| Characteristic | Value |
|---|---|
| Range / device | Acti9 iC60 / iC60N |
| Poles | 1P (1 protected pole) |
| Rated current [In] | 25 A |
| Tripping curve | C |
| Trip unit | Thermal-magnetic |
| Networks | AC 50/60 Hz and DC |
| Isolation | Suitable for isolation (IEC/EN 60898-1, 60947-2) |
| Utilisation category | A |
Ultimate Breaking Capacity (Icu) and Service Breaking Capacity (Ics)
| Voltage | Icu (IEC/EN 60947-2) | Ics |
|---|---|---|
| 220–240 V AC | 10 kA | 7.5 kA (75%) |
| 100–133 V AC | 20 kA | 15 kA (75%) |
| 12–60 V AC | 36 kA | 27 kA (75%) |
| 12–60 V DC | 15 kA | 15 kA (100%) |
| 60–72 V DC | 10 kA | 10 kA (100%) |
IEC/EN 60898-1 rating: Icn 6000 A at 230 V AC (Ics 100%).
Dielectric Ratings
- Rated insulation voltage [Ui]: 500 V AC
- Rated impulse withstand voltage [Uimp]: 6 kV
- Energy limiting class: 3
Mounting, Wiring and Dimensions
The breaker is a single 18 mm module (85 × 78.5 mm) that clips onto a DIN rail. It accepts comb busbars at the top or bottom. Its terminals take 1–25 mm² rigid or 1–16 mm² flexible conductors, with a 14 mm stripping length and a 2 N·m tightening torque. A trip indicator and positive contact indication show the breaker’s state at a glance.
Operating Environment
- Operating temperature: −35 to 70 °C
- Protection: IP20
- Pollution degree: 3
- Overvoltage category: IV
- Durability: 20,000 mechanical / 10,000 electrical cycles
Compliance
The breaker complies with IEC/EN 60898-1 and IEC/EN 60947-2 and carries the NF mark. It is a Schneider Electric Green Premium product, RoHS and REACH compliant.
Acti9 iC60N 1P Neighbours
- A9F74120: 1P 20 A, C curve
- A9F77125: iC60N 1P 25 A C-curve breaker listed under another regional reference
- A9F74225: 2P 25 A, C curve
Buy the A9F74125 Schneider Electric from Atlantech Drives
Atlantech Drives supplies genuine Schneider Electric A9F74125 Acti9 iC60N breakers, together with comb busbars and Acti9 auxiliaries, with fast worldwide shipping. Our senior commercial team will confirm the right rating, curve and breaking capacity for your board and give you a competitive quote quickly.